Application
OA intelligent office building, places require wire planning and allocation
Characteristics
- Organize heavy wires
- Assembly agility
- Long service life
- Convenient removing & good exchangeability
Trucking type
Technical parameters
The raised floor will be with a safety factor of three times the concentrated (design) load, and is capable of meeting static and dynamic loads per CISCA Platform (Raised Access) Floors Performance Specification.
Type | Size | Uniform Load | Concentrated Load | Rolling Load | Impact Load | Ultimate Load | ||
0.100”/2.5mm Deflection | 10 Times | 10K Times | ||||||
FS450 | 500*500*28mm | 8.00KN/㎡ | 2.00KN | 204KG | 1.78KN | 1.56KN | 75LB/34KG | 6.89KN |
FS662 | 500*500*28mm | 11.77KN/㎡ | 2.94KN | 300KG | 2.45KN | 2.00KN | 100LB/45KG | 8.85KN |
FS800 | 500*500*28mm | 14.22KN/㎡ | 3.56KN | 363KG | 2.94KN | 2.45KN | 100LB/45KG | 11.25KN |
FS1000 | 500*500*28mm | 17.78KN/㎡ | 4.45KN | 454kG | 3.56KN | 2.67KN | 150LB/68KG | 14.50KN |
Why network raised floor?
Mordern offices need to adapt different layouts with different users and lessees, traditional facilities always become obsolete due to wiring and wiring distribution problems created by organisational changes and advances in technology, so building designers and facility managers need to face the challenges of constantly changing space needs while keeping life-cycle costs down.
Steel raised floor systems can realize fast and easy installation, quick wire and cable changes, enhancing the ability to reconfigure the offices without disrupting power, voice and data services, as well as the air distribution systems.